Optimal Media Replaceable V-pack Filter
Applications:fine particle filtration and pre-filtration for absolute filters
Type:multi-v packs filter
Frame:galvanized steel
Filter media:double layers complex synthetic paper
Separators:continuous thermoplastic cord
Sealant:synthetic compact media
EN 779 Class:F6-F8
Average arrestance:99%(ASHRAE 52.1-1992)
MERV:MERV 11-15(ASHRAE 52.2-1999)
DIN 53438 Flammability:F1
UL 900 Standard:CLASS 2
Final pressure drop:(recommender) 450Pa
Max. air flow rate:125% of nominal air flow rate
Max. operating temperature:60℃
Max. relative humidity:80%
Type |
Class |
Dust Spot |
Dimensions |
Filtering |
Rated |
Initial pressure |
||
Length |
Height |
Depth |
||||||
VXT-65 |
F6 |
60-65% |
592 |
287 |
292 |
8.20 |
1700 |
120 |
VXT-65 |
F6 |
60-65% |
592 |
592 |
292 |
16.6 |
3400 |
120 |
VXT-65 |
F6 |
60-65% |
610 |
610 |
292 |
19.9 |
4000 |
120 |
VXT-85 |
F7 |
80-85% |
592 |
287 |
292 |
8.20 |
1700 |
140 |
VXT-85 |
F7 |
80-85% |
592 |
592 |
292 |
16.6 |
3400 |
140 |
VXT-85 |
F7 |
80-85% |
610 |
610 |
292 |
19.9 |
4000 |
140 |
VXT-95 |
F8 |
90-95% |
592 |
287 |
292 |
8.20 |
1700 |
160 |
VXT-95 |
F8 |
90-95% |
592 |
592 |
292 |
16.6 |
3400 |
160 |
VXT-95 |
F8 |
90-95% |
610 |
610 |
292 |
19.9 |
4000 |
160 |